Explanation of Function
Seite 83 / 180
Automatic energy-saving operation function
This function regulates the inverter output power automatically to a
minimum while operating at constant speed.
This fits for the load of reduced torque characteristic of fans or pumps.
In case of operating by this function, set A085 to “01”.
A086 can adjust the automatic operation, response time.
Set item
Function code
Deta
Contents
00 Normal
operation
Operation
mode
selection
A085
01
Energy-saving
operation
Set item
Function
code
Deta Response Accuracy
Energy saving
Response / accuracy
Adjustment
A086
0
100
Slow
Fast
High
Low
Two-stage Acceleration and Deceleration Function
By setting this function, it is possible to change the rate of
acceleration and deceleration.
As methods to change the rate of acceleration and deceleration,
you can select the method of changing by intelligent input terminal
and the method of automatic changing by optional frequency.
In case of changing by intelligent input terminal, assign 09(2CH) to
an Intelligent input terminal.
Set item
Function
code
Data Contents
Acceleration
time 2
A092/A292/
A392
0.01-3600. Unit : second (Example1,2)
Deceleration
time 2
A093/A293/
A393
0.01-3600. Unit : second (Example1,2)
00
Changing by intelligent input terminal 09 (2CH) (Example1)
Two-stage
acceleration
and
deceleration
selection
A094/A294
01
Changing by two-stage acceleration and deceleration
frequency (A095/A295, A096/A296) (Example2)
Two-stage
acceleration
A095/A295 0.00-400.0
Unit: Hz It is valid when two-stage acceleration and
deceleration selection (A094/A294) is 01. (Example2)
F002/F202/F302: 1
st
/2
nd
/3
rd
acceleration 1
F003/F203/F303: 1
st
/2
nd
/3
rd
deceleration time 1
A092/A292/A392: 1
st
/2
nd
/3
rd
acceleration time 2
A093/A293/A393: 1
st
/2
nd
/3
rd
deceleration time 2
A094/A294: 1
st
/2
nd
two-stage acceleration
and deceleration selection
A095/A295:1
st
/2
nd
two-stage acceleration
frequency
A096/A296: 1st/2
nd
two-stage deceleration
Relation
A085:Operation mode selection
A086:Energy-saving response-
Accuracy adjustment
Relation code