Explanation of Function
Seite 56 / 180
4.3.2 Function mode
Setting of the output frequency
Setting the output frequency of the motor.
The output frequency is set by F001, when the frequency command
select (A001) is set to 02.
Please refer to the frequency command select (A001) about other
methods of frequency setting.
When a frequency is set in F001, the same value is automatically set in 1
st
multi-stage zero speed (A020).
Set up with F001 in the condition where turned on the SET terminal, whether or not it sets up with the 2nd
multi-stage zero speed (A220)/ the 3rd multi-stage zero speed (A320), in the case that the 2nd/3rd control is
set up.
In the case of using SET/SET3, you will need to assign 08(SET)/17(SET3) to an intelligent input terminal.
Set item
Function
code
Data Contents
Output
frequency
F001
Multistage
speed zero
A020/A220/
A320
0.0, start
frequency-First/Second
highest frequency
Unit : Hz
“F001” = “A020”
Second control setting of “F001” =
“A220”
Third control setting of “F001” =
“A320”
Operation direction
This is effective when the operating command is set by the digital operator.
Function
code
Data Contents
00 Forward
F004
01 Reverse
Selection with limits of operation direction
The direction of the motor can be restricted.
Function code
Data
Contents
00
Forward/reverse is
Effective.
01
Only forward
b035
02 Only
reverse
Frequency command selection
Select the method of frequency command.
When 0-10Vdc is inputted to the frequency command by 02-L terminal, operation direction of motor
reverses.
On output frequency monitor d001, you can’t get information about forward/reverse. So be sure with
operation direction monitor d002.
F004: Operation direction
select
Relation
F001 :Output frequency
A001 :Frequency command select
A020/A220/A320: 1st/2nd/3rd multistage
speed zero
Relation code
b035: Selection with limits
of operation direction
Relation
A001:Frequency command
selection