Explanation of Function
Seite 128 / 180
Stabilized factor
When the motor is hunting or unstable, this function can be adjusted to help
stabilize the motor.
When the motor is unstable, check the allowable motor selection (H003/H203) and motor pole selection
(H004/H204) with your motor. If their code data is different from your motor specification, set the right data.
When R1 of usage motor is less than R1 of regular motor, raise the set value of H006/H206 gradually.
When you operate greater motor than rated capacity of inverter, lower the set value of H006/H206.
The following two functions can also assist to reduce hunting or rattling of a motor.
(1) Lower the carrier frequency (b083).
(2) Lower the output voltage gain (A045).
Set item
Function code
Data
Description
Output gain
A045
20. -100.
Units :%
Lower this when hunting occurs.
Carrier
frequency
b083 0.5-15.0
Units :kHz
Lower this when hunting occurs.
Stabilized
factor
H006/H206/H
306
0. -255.
Raise or lower when hunting occurs.
Operation selection on option error
When an add-in option is the cause of a protective trip this function can be
Used to switch the trip facility off and allow the Inverter to carry on in it’s
Operation.
Set item
Function
code
Data Description
00
TRP: inverter trip and output alarm when option error
occurs.
Operation selection
on optional error
P001/P002
01
RUN: inverter ignores this and continues operation
when
option error occurs.
Motor constant
Set each constant according to the motor you use.
In case of using several motors in parallel, set the constant values that are closest to the total capacity of
the belonging motor.
Reduced torque or instability may occur while using auto torque boost function if these settings are
incorrect.
P001: Option1 operation
selection
on error
Relation
H006/H206/H306: 1st/2
nd
/3
rd
Relation code
H003/H203: 1
st
/2
nd
allowable motor
selection
Relation