Explanation of Function
Seite 137 / 180
A001
Frequency commanding method
A044
Control method
F001
Output frequency setting
b040
Selection of torque limit
b041-b044
Torque limit of 4zone
H002
H202
Selection of first, second
motor constant
H003
H203
Selection of first, second
motor capacity
H004
H204
Selection of first, second
motor pole
H005
H205
First, second speed response
H020
H220
First, second motor constant R1
H021
H221
First, second motor constant R2
H022
H222
First, second motor constant L
H023
H223
First, second motor constant I0
H024
H224
First, second motor constant J
H050
H250
First, second PI proportion gain
H051
H251
First, second PI integration
gain
H052
H252
First, second P proportion gain
SENSORLESS VECTOR CONTOROL
û
This function is the method that the revolution of motor and output torque are
estimated by output current, voltage of the inverter and motor constant of setting.
It is possible to operate high starting torque and high accuracy at law
frequency(0.5Hz).
û
In the case of using this function, please set 003 in A004.
û
In the case of using this function, please set surely the suitable motor constant
of using the motor according to the parameter of “selection of motor constant” .
Caution!
û
If the inverter operates less than twice capacity for the maximum adopted motor,
the full performances may not be demonstrated.
û
If satisfactory performance can not be obtained, please adjust the motor
constant for the phenomena according to following table;
Status of
running
Phenomena
Contents of adjustment
Adjusting
parameter
Speed fluctuation is
minus
Set “Motor constant R2”bigger and bigger slowly until 1.2
times for preset constant.
H021,H221
Driving
Speed fluctuation is
plus
Set “Motor constant R2” smaller and
smaller slowly until 0.8 times for preset constant.
H021,H221
Set “Motor constant R1”bigger and bigger
slowly until 1.2 times for preset constant.
H020,H220
Regeneratin
g
Lack of torque at low
frequency
Set “Motor constant I0” bigger and bigger slowly until 1.2
times for preset constant.
H023,H223
At
starting
The shock is occurred at
starting
Set “Motor constant J” bigger and bigger slowly until 1.2
times for preset constant.
H024,H224
Set speed response smaller.
H005,H205
At
deceleration
Unstable of motor
rotation
Set “Motor constant J” smaller for preset
Constant.
H024,H224
During
torque limit
Insufficient torque
during torque limit
at low speed
Set overload restriction level lower than torque limit level
b021
b041-b044
At low
frequency
operation
Irregular of rotation
Set “Motor constant J” bigger for preset constant.
H024,H224
Reference code