Explanation of Function
Seite 120 / 180
A044/A244
/A344
: First/second/third contro
method
selection
C021
-
C025
: Intelligent output selection
C055
: Over torque level
(forward driving)
C056
: Over torque level
(reverse regenerating)
C021 - C025
Intelligent output selectio
C062
Alarm code selection
OVER TORQUE (OTQ)
This function can detect that estimated value of output torque of
motor increase more than optional level and outputs.
When over torque signal is selected in intelligent output
selection, this function is valid.
This function is valid just when sensorless vector control, 0 Hz
domain sensorless vector control, or vector control with sensor
is selected. Make sure that output is unstable except these
controls.
Setting item
Function
code
Setting range
contents
Intelligent output selection
C021 -
C025
07
OTQ: Over toeque signal
Over torque level (reverse driving) C055
0. - 200.
Unit : %
Over torque level(forward
regenerating)
C056
0. - 200.
Unit : %
Over torque level (reverse driving) C057
0. - 200.
Unit : %
Over torque level (forward
regenerating)
C058
0. - 200.
Unit : %
ALARM CODE OUTPUT(AC0 – AC3)
This is the function that inverter outputs trip factor as signal.
When 01(3bit) or 02(4bit) is selected in alarm code selection,
intelligent output terminal , 11 – 13 or 11 – 14 compulsorily is outputted in alarm code.
Alarm code output is the following below.
Intelligent output terminal
In 4bit code selection
In 3bit code selection
14 13 12 11
AC3 AC2 AC1 AC0
Factor code
Contents of trip
Factor
code
Contents of trip
0 0 0 0
Normal
Normal
Normal Normal
0
0
0
1
E01 - E03
Over current protection
E01 - E03
Over current protection
0 0 1 0
E05
Overload
protection
E05
Overload
protection
0 0 1 1
E07,E15
Over voltage
Power source over voltage
protection
E07,E15
Over voltage
Power source over
Voltage protection
0
1
0
0
E09
Lack voltage protection
E09
Lack voltage protection
0 1 0 1
E16
Instantaneous power-
failure protection
E16
Instantaneous power
failure protection
0
1
1
0
E30
IGBT error
E30
IGBT error
0 1 1 1
E06
Braking resister overload
protection
1
0
0
0
E08,E11
EEPROM error, CPU error
1 0 0 1
E10
CT
error
1 0 1 0
E12,E13,E35
External trip, USP error,
thermistor error
1 0 1 1
E14
Grand
fault
protection
1 1 0 0
E17,E18,E25,E26 Connecting
error
1 1 0 1
E21
Power
module
temperature
1 1 1 0
E24
Phase
failure
protection
1 1 1 1
E50
-
E79
RS485
d
option 1,2 error 0 - 9
Relation
Relation