Explanation of Function
Seite 54 / 180
Accumulated time monitor on RUN
The operation time of inverter is accumulated and the value is displayed.
(Display)
0. - 9999. : Display is in 1 hour units.
1000 - 9999 : Display is in 10 hour units.
{100 - {999 : Display is in 100 hour units.
Power ON time monitor
This accumulates the time running to the inverter and displays the value.
(Display)
0. - 9999. : Display is in 1 hour units.
1000 - 9999 : Display is in 10 hour units.
{100 - {999 : Display is in 100 hour units.
Trip time monitor
This displays the number of inverter trips.
(Display)
0. - 9999. : Display is in 1 times unit.
1000 - 6553 : Display is in 10 times unit.
Trip monitor 1-6
This displays the details for the last six protective trips.
The trip monitor 1 displayed the details of the last trip.
(Display contents)
[1] Trip Code (Display anything from E01 to E79.)(Notes1)
[2] Output frequency on tripping (Hz)
[3] Output current on tripping (A)
[4] The direct voltage (between P and N) on tripping (V)
[5] The accumulated time inverter was operating until tripping (hr)
[6] The accumulated time inverter was run until tripping (hr)
(Note 1) Please refer to the pages 4.4 Protection function list (2) Trip monitor display.
d016: Accumulated time
monitor on RUN
Relation code
d017: Power ON time monitor
Relation code
d080: Trip time monitor
Relation
d081: Trip monitor 1
d082: Trip monitor 2
d083: Trip monitor 3
d084: Trip monitor 4
d085: Trip monitor 5
Relation