Explanation of Function
Seite 115 / 180
Output terminal a/b (NO/NC)selection
This sets the intelligent output terminal 11-15 and alarm relay
output terminal contact condition to either NO or NC, (a or b).
Each output is changeable individually.
Both intelligent output terminals 11 and 12 and the alarm relay are all relay outputs.
Set item
Function code
Data
Description
00
A
contact(NO)
Intelligent output
11-15
A/b(NO/NC) selection
C031-C035
01
B contact(NC)
00
A
contact(NO)
Alarm relay output
A/b(NO/NC)selection
C036
01
B contact(NC)
a contact: Close with {ON}, open with {OFF}.
b contact: Open with {ON}, close with {OFF}.
(1) Specification of the intelligent output terminals 11 - 15
Specification of the intelligent output terminals 11 - 15 is as follows;
C031-C0
35
Set value
Power
supply
Output
description
State of output
terminal 11 - 15
terminal
ON Close
On
OFF Open
00
(a
contact)
Off
-
Open
ON Open
On
OFF Close
01
(b
contact)
Off
-
Open
Inverter
15 CM
1
- - - - - -