Installation and Wiring
Seite 27 / 180
(4) Common applicable tools
Applicable tools
Power lines
R,S,T,U,V,
W,P,PD,
External resister
Between
P and RB
Motor
Output
(kW)
Applicable
Inverter
model
mm
2
or
more
AWG
or
more
mm
2
AWG
Screw
size of
terminal
Terminal
Torque
(Nm)
Leak breaker
(ELB)
Circuit
breaker
Electro
-magnetic
controller
(Mg)
1.5 V3000-015LF 2
14 2 14 M4 2-4 1.5
EX30(15A)
10A H10C
2.2
V3000-022LF
2 14 2 14 M4 2-4
1.5
EX30(20A)
15A H20
3.7
V3000-037LF
3.5 10 3.5 10 M4 3.5-4
1.5
EX30(30A)
20A H20
5.5
V3000-055LF
5.5 8 5.5 8 M5 5.5-5
2.5
EX50B(50A)
30A H25
7.5
V3000-075LF
8 6 5.5 8 M5 8-5 2.5
EX60B(60A)
40A H35
11
V3000-110LF
14 4 5.5 8 M6 14-6
4.9
RX100(75A)
60A H50
15 V3000-150LF 22 2
-
-
M6 22-6 4.9
RX100(100A)
80A H65
18.5 V3000-185LF 30
1
-
-
M6 30-6 4.9
RX100(100A)
100A H80
22 V3000-220LF 38 1/0 -
-
M8 38-8 8.8
RX225B(150A)
125A H100
30 V3000-300LF 60 2/0 -
-
M8 60-8 8.8
RX225B(200A)
150A H125
37 V3000-370LF
100
(38x2)
(
#1
) - - M8
100-8
8.8
RX225B(225A)
175A H150
45 V3000-450LF
100
(38x2)
(
#2
) - - M10
100-1
0
-
RX225B(225A)
225A H200
200V
cl
ass
55 V3000-550LF
150
(60x2)
(
#3
) - - M10
150-1
0
-
RX400B(350A)
250A H250
1.5 V3000-015HF 2
18 2 18 M4 2-4 1.5
EX30(10A)
10A H10C
2.2
V3000-022HF
2 16 2 16 M4 2-4
1.5
EX30(10A)
10A H10C
3.7 V3000-037HF 2
14 2 14 M4 2-4 1.5
EX30(15A)
15A H20
5.5 V3000-055HF 2
12 2 12 M5 2-5 1.5
EX50C(30A)
15A H20
7.5 V3000-075HF 3.5 10 3.5 10
M5 3.5-5
1.5
EX50C(30A)
20A H20
11
V3000-110HF
5.5 8 5.5
8 M6 5.5-6
1.5
EX50C(50A)
30A H25
15 V3000-150HF 8
6
-
-
M6 8-6 4.9
EX60B(60A)
40A H35
18.5 V3000-185HF 14
6
-
-
M6 14-6 4.9
EX60B(60A)
50A H50
22 V3000-220HF 14
4 - - M6 14-6
4.9
RX100(75A)
60A H50
30 V3000-300HF 22
3 - - M6 22-6
4.9
RX100(100A)
70A H65
37 V3000-370HF 38
1 - - M6 38-6
4.9
RX100(100A)
90A H80
45 V3000-450HF 38
1 - - M8 38-8
8.8
RX225B(150A)
125A H100
400V
cl
ass
55 V3000-550HF 60
1/0 -
- M8 60-8 8.8
RX225B(175A)
125A H125
#1
3/0 or 2 parallel of 1A
#2
250kcmil or 2 parallel of 1 AWG(75 deg.)
#3
350kcmil or 2 parallel of 1/0 AWG
Note
: Field wiring must be made by a UL-listed and CSA-certified closed-loop terminal connector sized
for the wire gauge involved. Connector must be fixed by using the crimping tool specified by the connector
manufacture
Use suitable circuit breaker listed in this manual for UL’s listing purpose.
Otherwise, there is a danger of fire.
WARNING