Explanation of Function
Seite 135 / 180
MOTER CONSTANT SELECTION
Motor constant used in sensorless vector control and 0Hz domain sensorless vector control can be selected from the following the three.
(1) WATT general purpose motor constant
(2) Motor constant measured in offline autotuning
(3) Optional setting motor constant
Setting item
Function code
Setting range
Contents
First / second / third control
method
A044/A244/A344
00
01
02 (Note)
03 (Note)
04 (Note)
05 (Note)
Constant torque characteristics
Reduced torque characteristics
V/F free setting
Sensorless vector control
0 Hz domain sensorless vector control
FB optional vector control
First / second motor constant
selection
H002/H202
00
01
02
WATT general purpose motor constant
Autotuning constant
Autotuning constant
(online autotuning valid
First / second motor capacity
selection
H003/H203
0.2 - 55.0
Unit : kW
First / second motor pole
selection
H004/H204
2/4/6/8
Unit : pole
First / second motor constant R1
H020/H220
0.000 - 65.53
Unit :
First / second motor constant R2
H021/H221
0.000 - 65.53
Unit :
First / second motor constant L
H022/H222
0.00 - 655.35
Unit : mH
First / second motor constant Io
H023/H223
0.00 - 655.35
Unit :
First / second motor constant J
H024/H224
1.0 - 1000
Unit : kgm2
First / second autotuning
motor constant R1
H030/H230
0.000 - 65.53
Unit :
First / second autotuning
motor constant R2
H031/H231
0.000 - 65.53
Unit :
First / second autotuning
motor constant L
H032/H232
0.00 - 655.35
Unit : mH
First / second autotuning
motor constant Io
H033/H233
0.00 - 655.35
Unit :
First / second autotuning
motor constant J
H034/H234
1.0 - 1000
Unit : kgm2
Note) In first control method, it is possible to select setting range 00 - 05.
In second control method, it is possible to select setting range 00 - 04.
In third control method, it is possible to select setting range 00 - 01.
Optional setting of motor constant
When motor constant is set optionally, function code is as the following below.
First control is valid and motor constant is 00 Input H020 - H024 directly.
First control is valid and motor constant is 01/02 Input H030 - H034 directly.
Second control is valid and motor constant is 00 Input H220 - H224 directly.
Second control is valid and motor constant is 01/02 Input H230 - H234 directly.
When offline autotuning is not executed, in H030/H230 - H034/H234, the same frame constant as the constant
(WATT general purpose motor constant) is set
.