Explanation of Function
Seite 117 / 180
Signal during run (RUN)
This function is to provide an output signal when the Inverter is in a running
condition.
Assign 00(RUN: signal during run) to an intelligent output terminal 11 - 15 or the alarm relay output terminal.
The signal is still outputted when the dc braking operates.
Operation is as follows;
Frequency arrival signal (FA1, FA2, FA3, FA4, FA5)
When the output frequency arrives at the set frequency, an arrival signal is
outputted.
Assign 01(FA1:constant speed arrival signal), 02(FA2:over setting frequency),
06(FA3: only setting frequency), 24(FA4:over setting frequency 2), or 25(FA5:
only setting frequency 2) to an intelligent output terminal 11-15 or the alarm
relay output terminal.
Hysteresis frequency arrival signal is the following.
When ON : ON with (1% of setting frequency – maximum frequency)(Hz)
When OFF: OFF with (2% of setting frequency – maximum frequency)(Hz)
However in to set 06(FA3), 25(FA5) case when inverter accelerate.
When ON :(1% of setting frequency – maximum frequency)(Hz)
When OFF: (2% of setting fre maximum frequency)(Hz)
When inverter decelerates
When ON : (1% of setting fre maximum frequency)(Hz)
When OFF: (2% of setting frequency – maximum frequency)(Hz)
Set item
Function
code
Data (Hz)
Description
0.0
Don’t output arrival signal on
acceleration.
Acceleration
arrival
frequency
C042 / C045
0.01-400.0
Output arrival signal on acceleration.
0.0
Don’t output arrival signal on
deceleration.
Deceleration
arrival
frequency
C043 / C046
0.01-400.0
Output arrival signal on deceleration.
C021-C025: Intelligent output
Relation code
RUN
Output
C021-C025: Intelligent output
terminal
C042: Acceleration arrival
frequency
Relation