Explanation of Function
Seite 49 / 180
4.3 Explanation of function
4.3.1 Monitor mode
Output frequency monitor
Indication code d001 displays the frequency the inveter outputs.
The data is displayed as follows.
When d001 is displayed, the monitor lamp “Hz” is illuminated.
(Display)
0.00 - 99.99 : Display is in 0.01Hz unit.
100.0 - 400.0 : Display is in 0.1Hz unit.
Output current monitor
Indication code d002 displays the output current value.
The data is displayed as follows.
In case of displaying d002, the monitor lamp “A” is illuminated.
(Display)
0.0 - 999.9 : Display is in 0.1A unit.
Operation directon monitor
Indication code d003 displays the direction that the Inverter output is
Rotating. Forward, reverse or stop.
On operating the inverter (in case of forward or reverse), the RUN lamp
will illuminate.
(Display)
F : Forward
o : Stop
r : Reverse
d001: Output frequency
monitor
Relation
d002: Output current
monitor
Relation
d003: Operation direction
monitor
Relation