Explanation of Function
Seite 125 / 180
Initialization setting
It is possible at any time to reinitialize the Inverter parameters back to their factory
default. The trip history can also be cleared at any time, however, if problems occur it
will be difficult to fault find without the trip history for reference.
Initialization details are as follows;
Set item
Function
mode
Data Description
00
This clears only trip history.
01
This only initializes setting value.
Setting value becomes the state on factory
forwarding.
Initialization
selection
b084
02
This clears trip history and initializes setting.
00
Initializing setting for Japan.
01
Initializing setting for Europe
Initial data
Selection
b085
02
Initializing setting for America.
(Initialization methods)
After setting the above parameters, initialize as follows;
b084: initialization
selection
b085: Initial data
Relation code
POWER
%
A
ALARM
RUN
PRG
V
Hz
kW
1
2
WATT
MIN
MAX
STR
RUN
STOP/
RESET
FUNC
(1) Hold down the FUNC, UP and
DOWN key and then press the
STOP/RESET key. When the
display starts to flash and rotate
(2) During initializing
Above display is for Japan.
Other displays are below.
(3) When “d001” is displayed in the
monitor, initialization is complete.
The display revolves on the left.
During initializing for
During initializing of trip
During initializing for
%
A
ALARM
RUN
PRG
V
Hz
kW
1
2
WATT
MIN
MAX
STR
RUN
STOP/
RESET
FUNC
POWER
%
A
ALARM
RUN
PRG
V
Hz
kW
1
2
WATT
MIN
MAX
STR
RUN
STOP/
RESET
FUNC
POWER