Explanation of Function
Seite 139 / 180
A044/A244
First / second control method
C027
FM selection
C028
AM selection
C029
AM
`
selection
H003/H203
First / second motor capacity
selection
H004/H204
First / second motor pole
selection
TORQUE MONITOR FUNCTION
This is a function for monitoring motor presumed output torque
when sensorless vector control, 0Hz domain sensorless vector
control, and vector control with sensor are selected in selection
method.
When monitor is carried out in digital operator, select display
code d012.
When monitor is carried out in control terminal, refer to the explanation about another section of the chapter4, FM
terminal, AM terminal, or AMI terminal.
When control method is selected VC, VP1.7 power or free V/f setting, take care that this function is
invalid, and display or output signal of control terminal is unstable.
Torque monitor value of this function displays 100% output torque when the motor rotates at
synchronized
revolution in the rated frequency equivalent to the rated output of the motor.
This funcion presumes output torque prior to motor current, therefore error is about 20% when the
motor which output is same as inverter is used.
Setting item
Function
Code
Setting range
Contents
Control method selection
A044/A24
4
(00)
(01)
(02)
(03)
(04)
(05)
VC
VP1.7 power
Vf free setting
SLV (A344 is not)
0 Hz domain SLV (A344 is not)
V2 (A344 is not)
FM selection
C27
(00)
(01)
(02)
(03)
(04)
(05)
(06)
(07)
Output frequency
Output current
Output torque
Digital output frequency
Output voltage
Input electric power
Thermal load rate
LAD frequency
AM selection
C28
AM1selection C29
(00)
(01)
(02)
(04)
(05)
(06)
(07)
Output frequency
Output current
Output torque
Output voltage
Input electric power
Thermal load rate
LAD frequency
Motor capacity selection
H003/H2
03
0.20 - 75.0
Unit : KW
Motor pole selection
H004/H2
04
2/4/6/8
Unit : pole
Relation code