Explanation of Function
Seite 68 / 180
Setting analog input filter
Set the internal filter of the frequency setting signal of voltage or current
from the control terminals
It is important to first remove the source of the noise to the system.
When stable operation can not be achieved due to the effect of electrcal noise, set a larger value.
The response will be slower by setting a larger value. The limit of setting is about 10ms-60ms( set value :
1-30)
Function
code
Limit to set
Contents
A016
1.-30.
Can set with the 1 unit.
Output voltage gain
Regarding the voltage selected on A082 motor voltage selection as 100 %,
set the rate of the voltage which the inverter outputs for the voltage selected.
Function
code
Limit to set
Contents
A045 20.-100. Unit:%
A016: O, OI, O2 filter
Relation code
A045: Output voltage gain
A082: Motor voltage selection
Relation
A45
Motor voltage
selection
100
)
Maxim
um
Base
frequency