Specification
Seite 177 / 180
Intelligent
output
terminal
Signal during run(RUN), Frequency arrival type 1 signal(FA1)
Frequency arrival type 2
signal (FA2)
Overload advance notice signal(OL)
Output deviation for PID control(OD)
Alarm signal(AL)
Arrival signal for only setting frequency(FA3),Over
torque(OTQ),Instantaneous stop signal(IP),Under voltage signal(UV),Torque
limit(TRQ),RUN time over(RNT),ON time over(ONT),Thermal caution(THM),Brake
opning(BRK),Brake error(BER),Zero speed detect signal(ZS),Speed deviation
excessive(DSE)
Positioning completion(POK),Arrival signal for over setting
frequency2(FA4),Arrival signal for only setting frequency2(FA5),Overload advance notice
signal2(OL2),Alarm cord0-3(AC0-AC3)
Ou
tp
ut
Intelligent
monitor
output
terminal
Analog voltage output, analog current output, pulse line output
Display monitor
Output frequency, output current, frequency conversion value, trip history, input output
terminal state, input electric power, output voltage, motor torque
Other function
V/f free setting (7points), Upper / lower frequency limitter, Frequency jump, Curve
adjustable speed, Manual torque boost level / Braking point,Analog meter adjustment,
Starting frequency, Carrier frequency adjustment, Electronic thermal free setting, External
start/end (frequency/rate),Analog input selection, Trip retry, Reduced voltage start,
Overload restriction,energy-saving operation, Restarting after an instantaneous power
failure, Various kinds signal output, Initialization value setting, Automatic deceleration at the
time of the power supply block,AVR function,Fuzzy,Autotuning(Online/Offline),High torque
multi running(Sensor-less vector control with 1 inverters of 2 motors)
Carrier frequency
range
0.5 - 15kHz
Protection
function
Over-current, over-voltage, under-voltage, electronic thermal level, abnormal trouble,
ground fault current on starting, instantaneous stop, USP error, open-phase error, control
resistor overload, CT error, external trip, communication error
Frequency
temperature/Preservation
temperature/humidty
-10 to 50 degrees / -20 to 65 degrees / 20 to 90 % RH (installed with no dew conensation)
Vibration 5.9
m/s
2
(0.6G)
10-55Hz 2.0
m/s
2
(0.2G)
10-55Hz
Us
age
su
rr
oundin
Using place
Under 1,000m above sea level, indoors (installed away from corrosive gasses dust))
Paint color
Grey (Munsell 8.5YR 6.2/0.2)
Options
Vector control with sensor
Op
tio
n
Digital input
option
4 column BCD
16bit binary
Remote operator, copy unit, cable for each operator, braking resistor, regenerative control
unit, alternating reactor, D.C. reactor, EMC Mains filter, higher harmonic
control unit, LCR filter, applied control installation
Other options
Schematic mass
(kg)
3.5 3.5 3.5 3.5 5 5 12 12 12 20 30 30 50