4.
Secure the combustion chamber
cover.
Flow limiter
1.
Switch OFF the control unit, shut
off the cold water supply line and
drain the system.
2.
Undo Allen screws
A
.
3.
Remove flow switch
B
and the
flow limiter downwards.
4.
Check flow limiter
C
and replace it
in case of excessive scaling or
damage.
5.
Reinstall flow limiter
C
and flow
switch
B
.