1.
Switch ON the control unit and call
up the relay test:
Constant temperature control
unit:
K
+
d
press simultaneously for
at least 2 s.
a
/
b
press, until "
5
" is dis-
played.
Weather-compensated control
unit:
K
+
d
press simultaneously for
at least 2 s.
a
/
b
press, until "
Valve in mid-
dle pos.
" is displayed.
2.
Wait until the valve has moved into
its central position (approx. 5 s),
then switch OFF the main ON/OFF
switch "
8
" at the control unit.
3.
Drain the heating system via the
boiler fill & drain valve
A
.
Further details regarding the individual steps
(cont.)
31
Commissioning, inspection, maintenance
5592
817
GB
Service