1.
&
Boiler water temperature sen-
sor
Pull the leads off the boiler tem-
perature sensor and check the
resistance.
&
Comfort sensor
Pull plug
%
from the cable har-
ness at the control unit and check
the resistance.
&
Flow temperature sensor
Pull plug "X3" from the control
unit and check the resistance
across terminals "X3.4" and
"X3.5".
2.
Compare the actual sensor resis-
tance with the curve.
3.
Replace the sensor in case of
severe deviation.
Danger
The boiler water tempera-
ture sensor is immersed in
the heating water (risk of
scalding).
Drain the boiler before
replacing the sensor.
Repairs
(cont.)
92
Troubleshooting
5592
817
GB