Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
Control unit trans-
mits outside tem-
perature
Set
code "97:2"
Control unit re-
ceives outside tem-
perature
Set
code "97:1"
Control unit re-
ceives outside tem-
perature
Set
code "97:1"
—
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber
fault monitoring
Code "9C:20"
LON subscriber
fault monitoring
Code "9C:20"
—
Updating the LON subscriber list
Only possible if all subscribers are
connected and the control unit is pro-
grammed to be fault manager (code
"79:1").
Press the following keys:
1.
L
+
d
simultaneously for
approx. 2 s.
Subscriber check
initiated (see page 50).
2.
e
The subscriber list is
updated after approx.
2 min.
The subscriber check is
completed.
Carrying out a subscriber check
Communication with the system devices connected to the fault manager is
tested with a subscriber check.
Precondition:
&
The control unit must be pro-
grammed as
fault manager
(code
"79:1")
&
The LON subscriber number must
be programmed in all control units
(see page 49)
&
The LON subscriber list in the fault
manager must be up to date (see
page 49)
A
Consecutive number in the sub-
scriber list
B
Subscriber number
Further details regarding the individual steps
(cont.)
50
Commissioning, inspection, maintenance
5592
817
GB
Summary of Contents for VITOPEND 200
Page 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Page 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Page 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Page 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Page 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Page 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Page 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Page 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Page 130: ...130 5592 817 GB...
Page 131: ...131 5592 817 GB...