Parameter
Heating circuit pump
-4
-5 °C
-3 °C
-3
-4 °C
-2 °C
-2
-3 °C
-1 °C
-1
-2 °C
0 °C
0
-1 °C
1 °C
1
0 °C
2 °C
2
to
1 °C
to
3 °C
15
14 °C
16 °C
Coding in the delivered condition
Possible change
Boiler circuit, mixer circuit
A4:0
With frost protection
(only for weather-com-
pensated control units)
A4:1
No frost protection; this
setting is only possible if
code "A3:-9" has been
selected.
Note
Observe the information
regarding coding address
"A3"
A5:5
With heating circuit
pump logic function
(economy circuit): Heat-
ing circuit pump "OFF"
when the outside tem-
perature (AT) is 1 K
higher than the set
room temperature
(RT
set
)
AT > RT
set
+ 1 K (only
for weather-compen-
sated control units)
A5:0
Without heating circuit
pump logic function
A5:1
to
A5:15
With heating circuit pump
logic function: Heating
circuit pump "OFF" (see
the following table)
Parameter address
A5:...
With heating circuit pump logic function: Heating
circuit pump "OFF"
1
AT > RT
set
+ 5 K
2
AT > RT
set
+ 4 K
3
AT > RT
set
+ 3 K
Code 2
(cont.)
63
Coding
5592
817
GB
Service
Summary of Contents for VITOPEND 200
Page 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Page 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Page 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Page 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Page 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Page 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Page 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Page 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Page 130: ...130 5592 817 GB...
Page 131: ...131 5592 817 GB...