Changing the language (if required)
–
only for weather-com-
pensated control units
Note
When the unit is first taken into opera-
tion the display is in German (default
language setting):
Select heating circuit (see step 1.)
Outside temperature (see step 3.)
Press the following keys:
1.
c
"
Heizkreis wählen
" (select
heating circuit) is displayed.
2.
d
to confirm; wait approx. 4 s.
3.
c
press this button again,
"
Außentemperatur
" (outside
temperature) is displayed.
4.
b
for the required language.
5.
d
to confirm.
Checking the gas type
Note
The boiler is set up in the factory for natural gas E.
1.
Check the gas type and Wobbe
index (W
s
) with your gas supply uti-
lity or LPG supplier and compare
them with the details on the burner
label.
2.
Convert the burner in accordance
with the details provided by the gas
supply utility or the LPG supplier to
match the fuel provided, if these
details diverge.
Conversion kit installation
instructions.
3. For conversion to LPG
Adjust code "1E:1" (see coding
level 1 page 53).
Further details regarding the individual steps
(cont.)
22
Commissioning, inspection, maintenance
5592
817
GB
Summary of Contents for VITOPEND 200
Page 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Page 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Page 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Page 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Page 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Page 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Page 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Page 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Page 130: ...130 5592 817 GB...
Page 131: ...131 5592 817 GB...