Checking the temperature limiter
Check the temperature limiter if the burner control unit cannot be reset after a
fault shutdown, although the boiler water temperature is below approx. 90 °C
(display "
E
").
A
Temperature limiter
1.
Pull the leads from the temperature
limiter.
2.
Check the continuity of the tem-
perature limiter with a multimeter.
3.
Remove the faulty temperature lim-
iter.
4.
Coat the replacement temperature
limiter with heat conducting paste
and install it.
5.
After commissioning, press reset
button "
E
RESET" at the control
unit.
Repairs
(cont.)
94
Troubleshooting
5592
817
GB