Coding in the delivered condition
Possible change
FA:20
Raising the set boiler
water temperature or
the set flow temperature
when changing from op-
eration with reduced
room temperature to op-
eration with standard
room temperature by
20 %. See example on
page 110 (only for
weather-compensated
control units).
FA:0
to
FA:50
Temperature rise adjusta-
ble from 0 to 50 %
Fb:30
Duration for raising the
set boiler water tem-
perature or the set flow
temperature (see cod-
ing address "FA")
60 min. See example on
page 110 (only for
weather-compensated
control units).
Fb:0
to
Fb:150
Duration adjustable from
0 to 300 min;
1 step
≙
2 min
Resetting codes to their delivered condition
Press the following keys:
1.
L
+
G
simultaneously for
approx. 2 s.
2.
e
"
Standard setting?
Yes
" appears.
3.
d
to confirm
or
4.
a
/
b
to select "
Standard set-
ting? No
".
Code 2
(cont.)
70
Coding
5592
817
GB
Summary of Contents for VITOPEND 200
Page 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Page 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Page 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Page 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Page 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Page 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Page 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Page 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Page 130: ...130 5592 817 GB...
Page 131: ...131 5592 817 GB...