External heating program changeover
The "External heating program chan-
geover" function is connected via
external extension input "
aVD
". You
can select which heating circuits the
heating program changeover affects
in coding address "91":
Heating program changeover
Coding
No changeover
91:0
Heating circuit without mixer A1
91:1
Heating circuit with mixer M2
91:2
Heating circuit without mixer and heating circuit with mixer 91:3
You can select which direction the
heating program changes over in cod-
ing address "D5":
Heating program changeover
Coding
Changeover towards "Permanently reduced" or "Perma-
nent standby" mode (subject to the selected set value)
d5:0
Changeover towards "Constant heating mode"
d5:1
The duration of the heating program
changeover can be adjusted in coding
address "F2":
Heating program changeover
Coding
No heating program changeover
F2:0
Duration of the heating program changeover 1 to 12 hours
F2:1 to
F2:12
The heating program changeover
stays enabled for as long as the con-
tact remains closed, but at least as
long as the duration selected in cod-
ing address "F2".
Control functions
105
Function description
5592
817
GB
Service
Summary of Contents for VITOPEND 200
Page 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Page 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Page 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Page 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Page 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Page 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Page 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Page 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Page 130: ...130 5592 817 GB...
Page 131: ...131 5592 817 GB...