Fault
code
on the
display
Const.
Weath.-
comp.
System char-
acteristics
Cause
Measures
A7
X
Control mode
as per the de-
livered condi-
tion
Faulty pro-
gramming
unit
Replace program-
ming unit
b1
X
X
Control mode
as per the de-
livered condi-
tion
Communica-
tion fault,
program-
ming unit
Check connec-
tions and replace
the programming
unit, if required
b4
X
X
Regulates as
if the outside
temperature
was 0 °C
Internal fault
Replace the con-
trol unit
b5
X
X
Control mode
as per the de-
livered condi-
tion
Internal fault
Replace the con-
trol unit
b7
X
X
Burner
blocked
Boiler coding
card fault
Plug in boiler cod-
ing card or re-
place, if faulty
bA
X
Mixer regu-
lates to 20 °C
flow tempera-
ture
Communica-
tion fault, ex-
tension kit
for heating
circuit M2
Check the exten-
sion kit connec-
tions and
encoding; start
the extension kit
bC
X
Control mode
without remote
control
Communica-
tion fault
–
Vitotrol re-
mote control,
heating cir-
cuit A1
Check connec-
tions, cable/lead
and coding ad-
dress "A0"
bd
X
Control mode
without remote
control
Communica-
tion fault,
Vitotrol re-
mote control,
heating cir-
cuit M2
Check connec-
tions, cable/lead
and coding ad-
dress "A0"
Fault codes
(cont.)
83
Troubleshooting
5592
817
GB
Service
Summary of Contents for VITOPEND 200
Page 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Page 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Page 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Page 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Page 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Page 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Page 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Page 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Page 130: ...130 5592 817 GB...
Page 131: ...131 5592 817 GB...