9.
Open the gas shut-off valve and
start up the boiler.
Danger
Gas escaping from the test
port leads to a risk of explo-
sion.
Check the test connector for
soundness.
Supply (flow)
pressure for nat-
ural gas
Supply (flow)
pressure for
LPG
Measures
below 17.4 mbar
below 42.5 mbar
Do not start the boiler. Notify your
mains gas or LPG supplier.
17.4 to 25 mbar
42.5 to 57.5 mbar
Start the boiler.
above 25 mbar
above 57.5 mbar
Install a separate gas pressure gover-
nor upstream of the system and regu-
late the inlet pressure to 20 mbar for
natural gas or 50 mbar for LPG. Notify
your mains gas or LPG supplier.
Further details regarding the individual steps
(cont.)
26
Commissioning, inspection, maintenance
5592
817
GB