Fault
code
on the
display
Const.
Weath.-
comp.
System char-
acteristics
Cause
Measures
F0
X
X
Burner
blocked
Internal fault
Replace the con-
trol unit
F2
X
X
Burner in a
fault state
The tem-
perature lim-
iter has
responded
Check the heating
system fill level,
the circulation
pump, the tem-
perature limiter
and connecting
cables/leads; vent
the system; press
"
E
RESET"
F3
X
X
Burner in a
fault state
Flame signal
is already
present at
burner start
Check the ionisa-
tion electrode and
connecting cable;
press
"
E
RESET"
F4
X
X
Burner in a
fault state
No flame sig-
nal.
Check the ionisa-
tion electrode,
ignition, ignition
module, ignition
electrodes, con-
necting cable, gas
pressure and gas
train; test the ioni-
sation current;
press
"
E
RESET"
F5
X
X
Burner control
unit fault
The air pres-
sure switch
is closed
during the
burner start
or does not
close when
the ignition
load speed
has been
reached
Check the ba-
lanced flue sys-
tem, the air
pressure switch
hoses, the air
pressure switch
and connecting
leads
Fault codes
(cont.)
86
Troubleshooting
5592
817
GB
Summary of Contents for VITOPEND 200
Page 12: ...Opening the control unit casing 12 Installation sequence 5592 817 GB...
Page 16: ...Fitting the programming unit into the control unit 16 Installation sequence 5592 817 GB...
Page 17: ...Fitting the front panel 17 Installation sequence 5592 817 GB Installation...
Page 113: ...Connection and wiring diagram internal connections 113 Designs 5592 817 GB Service...
Page 119: ...Parts lists cont 119 Parts lists 5592 817 GB Service...
Page 120: ...Parts lists cont 120 Parts lists 5592 817 GB...
Page 121: ...Parts lists cont 121 Parts lists 5592 817 GB Service...
Page 122: ...Parts lists cont 122 Parts lists 5592 817 GB...
Page 130: ...130 5592 817 GB...
Page 131: ...131 5592 817 GB...