82
Plug
sYS
Terminals
Function
Explanation
212.2
A1
Heating circuit pump for
heating circuit without mixer
A1/HC1
■ If a heating water buffer cylinder is
installed, this pump will be installed in
addition to the secondary pump.
■ Connect temperature limiter as maxi-
mum temperature limiter for underfloor
heating circuit (if installed) in series
(see the following chapter).
Connection values:
■ Output: 100 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
212.3
DHW circulation pump
Connection values:
■ Output: 50 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
Connecting a temperature limiter as a maximum temperature limiter for under-
floor heating
Connecting a general temperature
limiter
B
M
1~
C
B
X2.N
?
A
X1.
Connecting the temperature limiter,
part no. 7151 728, 7151 729
B
M
1~
C
B
sÖ
X2.N
?
A
X1.
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5692 875 GB
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...