Main PCB
Information regarding the connection
values
■ The output given is the recommended
connected load.
■ The total output of all components con-
nected directly to the heat pump con-
trol unit (e.g. pumps, valves, message
facilities, contactors) must not exceed
1000 W.
If the total output is < 1000 W, the indi-
vidual output of a component (e.g.
pump, valve, messaging facility, con-
tactor) may be selected larger than
specified. However, the breaking
capacity of the corresponding relay
must not be exceeded.
■ The stated current indicates the max.
switching current of the switching con-
tact (observe the total current of 5 A).
■ Controls for external heat source and
central fault message are unsuitable
for safety LV.
Set the required parameters during commissioning; see from page 110.
230 V~ components
Plug
sYA
Terminals
Function
Explanation
211.1
Fan
Connection values:
■ Output: 200 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connected at the factory.
211.2
1.
Secondary pump
■ In systems without a heating water
buffer cylinder, no other heating circuit
pump is required (see terminal 212.2).
■ Connect the temperature limiter in ser-
ies as a maximum temperature limiter
for an underfloor heating circuit (if
installed; see page 82).
Connection values:
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Type AWCI-M-AC 301.A
:
Connected at the factory.
Type AWO-M-AC 301.A
:
Connect on site; installation in the sec-
ondary circuit flow.
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5692 875 GB
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...