13
Cables
A
C
D
G
E
H
F
K
B
A
Heat pump control unit
B
Power cable for heat pump control
unit 230 V/50 Hz
Recommended cable: 3 x 1.5 mm
2
(5 x 1.5 mm
2
with power-off by the
power supply utility)
C
Connection cables for further com-
ponents and functions (e.g. pumps,
sensors, fault messages etc.)
D
Two connecting cables, fully wired
(5, 15 or 30 m):
■
Control cable
230 V~
■
LV lead
< 42 V
E
Power cable for compressor/fan
(230 V/50 Hz; 1/N/PE)
Recommended cable: 3 x 4.0 mm
2
,
flexible
F
Power cable, instantaneous heating
water heater (if installed), max. out-
put 9 kW
Recommended cable:
230 V/50 Hz; 1/N/PE: 7 x 2.5 mm
2
,
flexible
G
Instantaneous heating water heater
(accessory)
H
Control panel
K
Internal heat pump
Required cable lengths:
■ For the heat pump control unit (wall
outlet centrally directly below the heat
pump control unit):
0.6 m from the wall outlet
■ Inside the heat pump (to the control
panel):
2.6 m from the cable entry
Preparing for installation
Internal heat pump, type AWCI-M-AC 301.A
(cont.)
5692 875 GB
Installation
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...