100
1.
Remove contact shield
C
.
2.
Route 230 V~ power cable through
cable fitting
B
and apply strain
relief.
230 V/ 50 Hz
N
1 / N / PE
L1
N
L3
L2
L1
A
?
?
3.
Connect cores to power supply ter-
minals
A
in the control panel.
4.
Fit contact shield
C
.
5.
If a seal is required (if economy tariff
with power-OFF is utilised), guide the
seal wire through holes
D
in both
studs.
■ On-site fuse protection in accordance
with the compressor rating (see spec-
ification).
Note
The upstream fuses must have B char-
acteristics.
■ No parameters need to be set when
using economy tariff with power-OFF.
During the power-OFF period, the
compressor is shut down.
■ Recommended power cable: Flexible
3 x 4.0 mm
2
for cable lengths up to
20 m. A larger cable cross-section is
required for cable lengths > 20 m.
Power supply with power-OFF
Power-OFF without on-site load dis-
connection
The power-OFF signal is connected
directly to the heat pump control unit.
The compressor is "forced" off when
power-OFF is enabled.
Parameter
"Output for instant. heating
water heater at power-OFF 790A"
determines whether and at what stage
the instantaneous heating water heater
(accessory) stays operational.
Installation sequence
Power supply
(cont.)
5692 875 GB
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...