145
Vitocal 300-A
Type
AWCI-M-
AC
301.A09
AWO-M-
AC
301.A09
AWO-M-
AC
301.A09
(Silent)
Heating water
at 10 K spread
Contents
litres
3.5
Min. flow rate
l/h
900
Pressure drop, condenser
mbar
25
Max. flow temperature at -20°C air
intake temperature
°C
35
Max. flow temperature at -5 °C air
intake temperature
°C
50
Electrical values
Rated voltage
1/N/PE, 230 V/50 Hz
Rated current (max.)
A
29
Starting current (with electronic start-
ing current limiter)
A
40
Starting current (with stalled arma-
ture)
A
97
Fuse protection
A
1 x B32A
Fan protection
6.3 AH (slow)
IP rating
–
IP X4
IP X4
Control circuit rated voltage
230 V/50 Hz
Control circuit protection
6.3 AH (slow)
Refrigerant circuit
Refrigerant
R 407 C
Fill volume
kg
5.1
Compressor
Type Hermetically sealed digital scroll with
bypass
Dimensions
■ Total length
mm
946
946
1265
■ Total width
mm
880
880
1380
■ Total height
mm
1870
1885
1885
Total weight
kg
289
279
309
Permiss. operating pressure
bar
3
3
3
Connections
Heating water flow and return
R 1½
R 1¼
R 1¼
Condensate hose (Ø internal/exter-
nal)
mm
25/32
25/32
25/32
Specification
Specification
(cont.)
5692 875 GB
Service
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...