92
Terminals
Function
Explanation
X3.12
X3.13
or at exter-
nal exten-
sion H1
Signal "External demand"
(external starting of com-
pressor and pumps, mixer
in control operation or
OPEN, changeover of
operating mode of several
system components)
Requires zero volt
N/O
contact:
■ Closed: Demand
■ Open: No demand
■ Breaking capacity 230 V, 2 mA
Note
■ These or other external functions, such
as swimming pool water heating, cas-
cade or external set value default can
alternatively be connected via external
extension H1.
Installation instructions "External
extension H1"
■ If a swimming pool water heating facility
is connected to external extension H1,
no other external function can be con-
nected to external extension H1.
X3.17
X3.18
Fuse F1 6.3A (slow)
X5/X7
Control cable 230 V~
Terminals for connecting cable to the con-
trol panel
Controller and sensor PCB
Note
■ Plug F11:
Nothing should be connected to plug
F11 on site.
■ Flow temperature sensor for heat-
ing circuit with mixer (M3):
The flow temperature sensor for one
heating circuit with mixer (M3) is con-
nected to the extension kit for heating
circuit with mixer (accessory).
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5692 875 GB
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...