108
Checking the refrigerant circuit for leaks
1.
Check the floor area, valves and all
visible solder joints for traces of oil.
Note
Traces of oil indicate a leaking refrig-
erant circuit. Have your heat pump
checked over by a refrigeration engi-
neer.
2.
Check the heat pump interior with a
refrigerant leak detector or leak
detecting spray for refrigerant leaks.
Filling and venting on the secondary side
!
Please note
To prevent equipment damage,
protect electrical components
inside the heat pump from escap-
ing liquids.
Note
Before filling the system, observe
VDI 2035 sheet 1.
Type AWO-M-AC 301.A
A
Type AWCI-M-AC 301.A
A
B
B
8.
A
Manual air vent valve
B
3-way diverter valve for "Central
heating/DHW heating"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 875 GB