91
Terminals
Function
Explanation
Note
■ No parameters need to be set.
■ The compressor is shut down "hard" as
soon as the contact opens.
■ The supply voltage to the relevant com-
ponents (subject to power supply utility)
is switched off by the power-OFF contact
signal.
■ The stages to be switched off can be
selected for the instantaneous heating
water heater (parameter "Output for
instant. heating water heater at
power-OFF").
■ The power supply of the heat pump con-
trol unit (3 x 1.5 mm
2
) and the cable for
the power-OFF blocking signal can be
run in one 5-core cable.
■ For further information regarding power-
OFF, see chapter "Power supply".
X3.8
X3.9
Contact humidistat
or
Jumper
Zero volt contact required:
■ Closed: Safety chain has continuity.
■ Open: Safety chain broken, heat pump
not operational.
■ Breaking capacity 230 V~, 0.15 A
Connect on site:
■ Connected in series if both safety com-
ponents are installed.
■
Insert jumper if no safety compo-
nents are installed.
X3.10
X3.11
Fault message, lag heat
pump in a cascade
or
Jumper
Zero volt contact required:
■ Closed: No faults
■ Open: Fault
■ Breaking capacity 230 V~, 0.15 A
There must not be a jumper when a mes-
sage contact has been connected.
Installation sequence
Electrical connections in the heat pump control…
(cont.)
5692 875 GB
Installation
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...