110
Equivalent to a static pressure of
1 bar.
3.
Top up with water until the filling pres-
sure exceeds the pre-charge pres-
sure of the expansion vessel.
On a cold system, the filling pressure
must be approx. 0.2 bar higher than
the static pressure.
4.
During commissioning, mark this
value on the pressure gauge as min-
imum filling pressure.
Checking the compressor casing temperature
1.
Switch ON the heat pump and oper-
ate it for at least 10 min.
2.
Measure the temperature of the com-
pressor casing exterior while it is in
operation.
The compressor must not develop a
layer of ice on its outside, and the
casing must not get hotter than
60 °C (if necessary, check with
Viessmann technical service).
Commissioning the system
Commissioning (configuration, parame-
ter settings and function checks) can be
carried out with or without the commis-
sioning assistant (see following chapter
and service instructions for the Vitotronic
200 heat pump control unit).
Note
Type and extent of parameters depend
on the heat pump type, on the selected
system scheme and the accessories
employed.
Commissioning with commissioning assistant
The commissioning assistant guides you
automatically through all the menus
where settings have to be made. For
this, "Coding level 1" is automatically
active.
!
Please note
Incorrect operation at "Coding
level 1" may result in damage to
the appliance and the heating
system.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 875 GB
Summary of Contents for Vitocal 300 AWO-M-AC 301.A
Page 5: ...5 Certificates Declaration of conformity 148 Keyword index 149 Index Index cont 5692 875 GB...
Page 47: ...47 Installation sequence Removing the transport brackets cont 5692 875 GB Installation...
Page 52: ...52 3x 3x 3x 3x 9 8 Installation sequence Fitting the outer panels cont 5692 875 GB...
Page 53: ...53 3x 10 3x 2x 11 Installation sequence Fitting the outer panels cont 5692 875 GB Installation...
Page 104: ...104 Fitting the front panel 1 2 2 Installation sequence Closing the heat pump cont 5692 875 GB...
Page 128: ...128 051 052 008 066 038 063 064 Parts lists Parts list type AWCI M AC 301 A cont 5692 875 GB...