Function Parameter Table VD560 Series Inverter User Manual
- 44 -
F0-13
Frequency
Upper Limit
Offset
0.00Hz~max frequency F0-10
0.00Hz
○
F0-14
Frequency
Lower Limit
0.00Hz~frequency upper limit F0-12
0.00Hz
○
F0-15
Frequency
Command
Resolution
2: 0.01Hz
2
●
F0-16
Frequency
Command
UP/DOWN
Reference in
Running
0: Running frequency
1: Set frequency
0
◎
F0-17
Digital Setting
Frequency
Memory
Selection when
Stop
0: No memory
1: Memory
0
○
F0-18
Acceleration
Time 1
0.00s~65000s
Model
dependent
○
F0-19
Deceleration
Time 1
0.00s~65000s
Model
dependent
○
F0-20
Acceleration/De
celeration Time
Unit
0: 1s
1: 0.1s
2: 0.01s
1
◎
F0-21
Acceleration/De
celeration Time
Reference
Frequency
0: Max frequency(F0-10)
1: Set frequency
2: 100Hz
0
◎
F0-22
Command
Source Bound
Frequency
Source
Unit’s digit: Operation panel command
binding frequency source selection
0: No binding
1: Digital setting frequency
2: AI1
3: AI2
4: AI3 (expansion card)
5: PULSE setting
6: MS reference
7: Simple PLC
8: PID
9: Communication setting
Ten’s digit: terminal command binding
frequency source selection, same as
above
Hundred’s digit: communication
command binding frequency source
selection, same as above
0x0000
○