Parameter Description VD560 Series Inverter User Manual
- 168 -
set the corresponding input terminals function to "counter input" (function 44), when the pulse
frequency is higher, must use DI5 port.
When the count vale reached set count value Fb-59, multi-function digital DO output "set count value
reached" ON signal, then the counter stop counting.
When the count value reached the designated count value Fb-60, multi-function digital DO output
"designated count value reached" ON signal, and the counter continue to count, the counter stop until
the " set count value".
Designated count value Fb-60 shall not be greater than set count value Fb-59. Below is the function
diagram for set count value reached and designated count value reached.
1
2
3
4
5
6
7
8
9
Count pulse
DI5
Set count
DO1
Designated count
relay
Fig 6-32 Schematic diagram of set count value and designated count value