VD560 Series Inverter User Manual Mechanical and Electrical Installation
- 31 -
OPEN
External
power
input
terminal
Connect to 24V by default, J14 jumper on main
control board to 24V or COM
connection.
When external power is used to drive DI1~DI5,
HDI1, OPEN needs to connect to the external
power supply and disconnect
J14(disconnecting with +24V/COM).
Communication
485+-485-
RS-485
communic
ation
terminals
Standard RS-485 communication terminal,
should use twisted pair cable
AI1-GND
Analog
input
terminal 1
1. Input Voltage range : DC 0V to 10V
2. Input resistance : 22kΩ
Analog Input
AI2-GND
Analog
input
terminal 2
Input range : DC 0V to 10V or 0/4mA~20mA,
can be selected by J5 jumper on main control
board, default DC0V~10V signal;
Input impedance: under voltage input-22 kΩ,
under current input 500Ω.
DI1-COM
Digital
input
terminal 1
DI2-COM
Digital
input
terminal 2
DI3-COM
Digital
input
terminal 3
DI4-COM
Digital
input
terminal 4
DI5-COM
Digital
input
terminal 5
1. Optical coupling isolation, compatible with
dual polarity input, internal resistance 3.3kΩ;
2. Multi-function digital input, through
F5-01-F5-05 to set function.
3. The inverter d24v power supply
built-in, COM is common terminal.
4. When using external power, JP14 should be
suspended, ex24V connect to OPEN
terminal, COM is common terminal(external
voltage supply range +24V±10%).
Digital Input
HDI1-COM
High
speed
pulse input
terminal
When used as general digit input, it is the
same function as DI1~DI5;
Can be combine with OPEN terminal as bipolar
high speed pulse input terminals, max input
frequency is 100kHz.
When use external power, input voltage range
+24V±10%;
The internal impedance 1.65 kΩ
AO1-GND
Analog
output
terminal 1
Support 0V~10V voltage or 0/4mA~20mA
current output, decided by jumper J3, default
0V~10V voltage output
Analog Output
Digital Output
AO2-GND
Analog
output
Support 0V~10V voltage or 0/4mA~20mA
current output, decided by jumper J4, default