Parameter Description VD560 Series Inverter User Manual
- 126 -
Din terminal must be closed before operating, then motor will run according to the previous memories
direction (initial running default forward), when receiving the Dix or DIy pulse rising single, the motor
will reverse running relative to before running direction, interval time more than the time set by F5-63,
receive the Dix or DIy pulse rising single again, the motor will reverse again, and that cycle repeats.
Fig 6-14 Back and forth control mode
F5-01
DI1 Terminal Function
Selection
1
◎
F5-02
DI2 Terminal Function
Selection
2
◎
F5-03
DI3 Terminal Function
Selection
4
◎
F5-04
DI4 Terminal Function
Selection
6
◎
F5-05
DI5 Terminal Function
Selection
8
◎
F5-06
HdI1 Terminal Function
Selection
0
◎
F5-07
DI7 (expansion card)
Terminal Function
Selection
0
◎
F5-08
DI8 (expansion card)
Terminal Function
Selection
0
◎
F5-09
DI9 (expansion card)
Terminal Function
Selection
0~63, see table blow
0
◎
This parameter is used to set the functions of the multifunctional digital input terminals.
Set
Value
Function
Description
0
No function
The terminals not being used can be set “no function”, to avoid
wrong operation.
1
Forward running
2
Reverse running
Via external terminals to control inverter forward reverse run