VD560 Series Inverter User Manual Parameter Description
- 193 -
b3-16
Target Voltage 1 Of AO2
0.500V
~
4.000V
Factory
Correction
○
b3-17
AO2 Measured Voltage 1 0.500V
~
4.000V
Factory
Correction
○
b3-18
AO2 Target Voltage 2
6.000V
~
9.999V
Factory
Correction
○
b3-19
AO2 Measured Voltage 2 6.000V
~
9.999V
Factory
Correction
○
The group function code, used to correct the analog output AO.
The group function parameters has been corrected before factory, when restore the factory, will revert
to the values after factory correction. Generally don't need to be corrected at the scene of the
application.
Target voltage is refers to the theory output voltage value of inverter. The measured voltage refers to
the actual voltage measure by the multimeter and other measurement instruments.
b3-20
AI2 Current Correction
Coefficient
0.0~200.0%
100.0%
○
b3-21
AI3 Current Correction
Coefficient
0.0~200.0%
100.0%
○
b3-22
AO1 Current Correction
Coefficient
0.0~200.0%
100.0%
○
b3-23
AO2 Current Correction
Coefficient
0.0~200.0%
100.0%
○
After adjusting the voltage and the hardware and softave are selected for current type, corrected
current through this set of parameter.