Function Parameter Table VD560 Series Inverter User Manual
- 62 -
F8-05
Motor 1
Overload
Pre-alarm
Coefficient
50%~100%
80%
○
F8-06
Overvoltage/ove
r current Stall
Mode Selection
0: Mode 0
1: Mode 1
0
◎
F8-07
Overvoltage Stall
Proportion Gain
0: Disabled
1~100
0
○
F8-08
Overvoltage Stall
Integral Gain
0~100
10
○
380VAC: 700.0VDC
F8-09
Overvoltage Stall
Protection
voltage
100.0VDC~800.0VDC
220VAC: 370.0VDC
○
F8-10
Over current
Stall Proportion
Gain
0: Disabled
1~1000
20
○
F8-11
Over current
Stall Integral
Gain
0~1000
20
○
F8-12
Over current
Stall Protection
Current
100%~200%
160%
○
F8-13
Quick Start Over
current
Suppression
Gain
0~1000
30
○
F8-14
Short-circuit to
Ground Upon
Power-on
0: Invalid
1: Valid
1
○
F8-15
Input Phase
Loss Protection
Selection
0: Disabled
1: Enabled
1
○
F8-16
Output Phase
Loss Protection
Selection
0: Disabled
1: Enabled
1
◎
F8-17
Offload
Protection
Selection
0: Invalid
1: Valid
0
○
F8-18
Offload
Detection Level
0.0~100.0%
10.0%
○
F8-19
Offload
Detection Time
0.0s~60.0s
1.0s
○
F8-20
Overspeed
Detection Value
(FVC)
0.0%~50.0% (max frequency)
20.0%
○