VD560 Series Inverter User Manual Parameter Description
- 113 -
F2 Motor 1 Parameter
F2-00
Motor Type Selection
0: Ordinary asynchronous motor
1: Frequency conversion asynchronous
motor
0
◎
F2-01
Rated Motor Power
0.1kW~1000.0kW
Model
dependent
◎
F2-02
Rated Motor Voltage
1V~2000V
Model
dependent
◎
F2-03
Rated Motor Current
0.01A~655.35A (Inverter power≤55kW)
0.1A~6553.5A (Inverter power>55kW)
Model
dependent
◎
F2-04
Rated Motor
Frequency
0.01Hz~max frequency
Model
dependent
◎
F2-05
Rated Motor Rotation
Speed
1RPM~65535RPM
Model
dependent
◎
The above function code for parameters of motor nameplates, whether using V/D control or vector
control, all need according to the motor nameplate set the related parameters accurately.
In order to obtain better performance of V/F or vector control, motor parameter tuning is required, and
the accuracy of the adjust results, close relation to correctly set motor nameplate parameters.
F2-06
Asynchronous Motor
Stator Resistance
0.001Ω~65.535Ω (Inverter
power≤55kW)
0.0001Ω~6.5535Ω (Inverter
power>55kW)
Tune
parameter
◎
F2-07
Asynchronous Motor
Rotor Resistance
0.001Ω~65.535Ω (Inverter
power≤55kW)
0.0001Ω~6.5535Ω (Inverter
power>55kW)
Tune
parameter
◎
F2-08
Asynchronous Motor
Leakage Inductive
Reactance
0.01mH ~655.35mH (Inverter
power≤55kW)
0.001mH ~65.535mH (Inverter
power>55kW)
Tune
parameter
◎
F2-09
Asynchronous Motor
Mutual Inductive
Reactance
0.1mH~6553.5mH (Inverter
power≤55kW)
0.01mH ~655.35mH (Inverter
power>55kW)
Tune
parameter
◎
F2-10
Asynchronous Motor
No-load Current
0.01A~F2-03 (Inverter power≤55kW)
0.1A~F2-03 (Inverter power>55kW)
Tune
parameter
◎
F2-06~F2-10 is the parameter of asynchronous motor, in generally the motor nameplate don’t have
these parameters, need through the inverter automatic tuning. Among them, the “asynchronous motor
static tuning” can only get the F2-06~F2-08 three parameters, and “asynchronous motor complete
tuning” besides can get here all five parameters, can also get the encode phase sequence, current
loop PI parameter etc.
Change the rated motor power (F2-01) or rated motor voltage (F2-02), the inverter will automatically
modify F2-06~F2-10 parameter values, return the five parameters for commonly used standard Y
series motor parameters.