Mechanical and Electrical Installation VD560 Series Inverter User Manual
- 18 -
Chapter 3 Mechanical and Electrical Installation
3.1 Installation Environment
The ambient temperature exerts great influences on the service life of the inverter and is not allowed
to exceed the allowable temperature range (-10
Celsius to 40
Celsius).
℃
℃
The inverter shall be mounted on the surface of incombustible articles, with sufficient spaces nearby
for heat sinking;
The inverter shall be mounted in locations free from direct sunlight;
The inverter shall be mounted in locations free from high humidity and condensate, Relative humidity
is lower than 95%;
The inverter shall be mounted in locations free from oil dirt, dust, and metal powder;
The inverter shall be mounted in locations free from corrosive gas, explosive gas or combustible gas.
3.2 The Installation Direction and Space
Install the inverter vertically so that the heat may be expelled from the top. to ensure the heat
dissipation space of the inverter
Fig 3.2-1 Inverter installation diagram
When Single Unit Installation: When the inverter power is not higher than 15kW, the size A can be
omitted. When the inverter power is higher than15kW, the size A shall be higher than 50mm.
When Installation of Upper and Lower Parts: When installing the upper and lower parts of the inverter,
the insulating splitter is required.
Mounting Dimension
Power Level
B
A
≤15kW
≥100mm
18.5kW-30kW
≥200mm
≥37kW
≥300mm
≥50mm