220
Firmware Version 5.4
Direct Injection: Pump Doesn’t Run
Power can be checked at multiple
locations. First is the connection at the
Injection module where the battery
power cable plugs in. The second
location is the output connection found
on the injection module. The third is
found at the 2 pin weather-pak tower
found on the injection cable PN:
4000851-3. See table below.
Check power connections
from the battery to the
injection pump
Refer to “calibrating
injection pump”
See “Boom sections
not turning blue” in
manual
Verify a target rate is
entered for the injection
control channel
Verify a value is
entered for the
active calibration
No
Yes
No
Yes
Boom indicators
turn blue on run
Summary of Contents for ag leader
Page 1: ...Operators Manual Firmware Version 5 4 Ag Leader PN 4002722 Rev G ...
Page 2: ...Firmware Version 5 4 ...
Page 20: ...6 Firmware Version 5 4 ...
Page 38: ...24 Firmware Version 5 4 For more information see Legend Settings on page 52 ...
Page 55: ...41 SETUP M ANAGEMENT S ETUP Remove button Press to remove a business ...
Page 56: ...42 Firmware Version 5 4 ...
Page 78: ...64 Firmware Version 5 4 ...
Page 82: ...68 Firmware Version 5 4 Press to Export All Log files Export All Log Files ...
Page 84: ...70 Firmware Version 5 4 ...
Page 94: ...80 Firmware Version 5 4 ...
Page 108: ...94 Firmware Version 5 4 ...
Page 140: ...126 Firmware Version 5 4 ...
Page 154: ...140 Firmware Version 5 4 ...
Page 158: ...144 Firmware Version 5 4 ...
Page 162: ...148 Firmware Version 5 4 ...
Page 222: ...208 Firmware Version 5 4 ...
Page 244: ...230 Firmware Version 5 4 ...
Page 260: ...246 Firmware Version 5 4 ...
Page 290: ...276 Firmware Version 5 4 ...
Page 304: ...290 Firmware Version 5 4 ...