
Service Manual for the Thermador Pro Grand Next Generation 48-Inch Natural Gas and LP Gas Ranges, Models:
PRG486JDG/01, PRL486JDG/01
58300000159722_ARA_EN_D
Page 39 of 92
6.7.5
XLO Valve Removal and Replacement
Extra low (XLO) valves are for the
left, front
,
left, rear
,
right,
front, and right, rear
burners. They are accessible from under the
maintop and require control panel removal.
NOTE:
The XLO valve used for the
right, front
burner also has extra
high (XHI) functionality, due to a larger orifice size.
Be sure to check QuickFinder for relevant information, documentation,
and the correct part number when replacing this component.
Figure 48: XLO Valve
1. Follow all safety precautions and steps in
2. Follow all steps in
Accessing Components under the Maintop
3. Remove the control panel (see
page
4. Detach the white side connector from the potentiometer by
pressing on the tab, then slide the potentiometer forward to
remove it from the valve shaft (see Figure 50, page 40).
5. Use an adjustable wrench to unscrew the large hex nut on the
solenoid and remove the XLO valve from the solenoid valve. Be
careful not to lose the plastic O ring positioned inside the large
hex nut of the solenoid valve, as it may fall out easily (see
Figure 45, page 37).
NOTE:
If you are not servicing the solenoid valve, leave it
attached to the gas tube, and leave its wire connectors attached.
6. From under the manifold, use a 1/4 inch wrench to remove and
retain the valve screw that secures the XLO valve onto the
manifold. Be careful not to lose the rubber washer attached to the
screw (see Figure 49).
7. Gently lift the protruding part of the XLO valve out of the
receptacle on the manifold. Don’t lose the red rubber washer
attached to the base of the valve.
8. Replace the XLO valve if needed.
Gas Leaks
With electrical power off, carefully check for gas leaks at each gas
component that was removed, replaced, or otherwise serviced using a
gas leak detector (electronic leak detectors are highly recommended)
or bubble test. For XLO valves, you may need the electrical power to
be on when testing for gas leaks.
Use extreme caution
when
performing gas leak testing on XLO valves with the electrical power
on.
Figure 49: Removing the Valve Screw