Principles of Operation
Teledyne API Model T360/T360M Operation Manual
214
Table 7-2: Relay Board Status LED’s
LED
COLOR
FUNCTION
STATUS WHEN LIT
STATUS WHEN UNLIT
D1 RED
Watchdog
Circuit
Cycles On/Off Every 3 Seconds under direct control of the
analyzer’s CPU.
D2
YELLOW
Wheel Heater
HEATING
NOT HEATING
D3
YELLOW
Bench Heater
HEATING
NOT HEATING
D4 YELLOW
Spare
N/A
N/A
D5 GREEN Sample/Cal Gas
Valve Option
Valve Open to CAL GAS
FLOW
Valve Open to SAMPLE GAS
FLOW
D6 GREEN Zero/Span Gas
Valve Option
Valve Open to SPAN GAS
FLOW
Valve Open to ZERO GAS FLOW
D7 GREEN Shutoff Valve
Option
Valve Open to CAL GAS
FLOW
Valve CLOSED to CAL GAS
FLOW
D8
GREEN
IR SOURCE
Source ON
Source OFF
STATUS LED’s
DC VOLTAGE TEST
POINTS
RELAY PCA
Figure 7-17:
Location of relay board Status LED’s
7.4.5.6.
I
2
C
WATCH DOG CIRCUITRY
Special circuitry on the relay board monitors the activity on the I
2
C bus and
drives LED D1. Should this LED ever stay
ON
or
OFF
for 30 seconds, the
watchdog circuit will automatically shut of all valves as well as turn off the IR
Source and all heaters. The GFC wheel motor will still be running as will the
Sample Pump, which is not controlled by the relay board.
07272B DCN6552
Summary of Contents for T360
Page 2: ......
Page 188: ...This page intentionally left blank 07272B DCN6552 ...
Page 264: ...07272B DCN6552 ...
Page 320: ...This page intentionally left blank B 2 07272B DCN6552 ...
Page 324: ...This page intentionally left blank B 6 07272B DCN6552 ...
Page 327: ...APPENDIX D Wire List and Electronic Schematics D 1 07272B DCN6552 ...
Page 328: ...This page intentionally left blank D 2 07272B DCN6552 ...
Page 332: ...This page intentionally left blank 07272B DCN6552 D 6 ...
Page 333: ...07272B DCN6552 D 7 ...
Page 338: ...07272B DCN6552 D 12 ...