Teledyne API Model T360/T360M Operation Manual
Operating Instructions
163
4.15.4.3. ACTIVATING HESSEN PROTOCOL
The first step in configuring the T360 to operate over a Hessen protocol network
is to activate the Hessen mode for com ports and configure the communication
parameters for the port(s) appropriately. Press:
SETUP X.X
PRIMARY SETUP MENU
CFG DAS
RNGE
PASS CLK
MORE
EXIT
SAMPLE* RANGE = 500.000 PPM CO2 =X.XXX
< TST TST > CAL
SETUP
SETUP X.X
SECONDARY SETUP MENU
COMM
VARS DIAG ALRM
EXIT
SETUP X.X
COMMUNICATIONS MENU
ID INET
COM1
COM2
EXIT
SETUP X.X
COM1 MODE:0
SET>
EDIT
EXIT
Continue pressing next until …
Select which
COMM
port to configure
SETUP X.X
COM1 QUIET MODE: OFF
NEXT
OFF
ENTR EXIT
SETUP X.X
COM1 HESSEN PROTOCOL : ON
PREV
NEXT
ON
ENTR EXIT
SETUP X.X
COM1 HESSEN PROTOCOL : OFF
PREV NEXT
OFF
ENTR EXIT
ENTR
accepts the new
settings
EXIT
ignores the new
settings
The sum of the mode
IDs of the selected
modes is displayed here
SETUP X.X
COM1 E,7,1 MODE: ON
PREV NEXT
ON
ENTR EXIT
SETUP X.X
COM1 E,7,1 MODE: OFF
PREV NEXT
OFF
ENTR EXIT
Toggle
OFF/ON
to
change
activate/deactivate
selected mode.
Repeat the entire
process to set up
the
COM2
port
07272B DCN6552
Summary of Contents for T360
Page 2: ......
Page 188: ...This page intentionally left blank 07272B DCN6552 ...
Page 264: ...07272B DCN6552 ...
Page 320: ...This page intentionally left blank B 2 07272B DCN6552 ...
Page 324: ...This page intentionally left blank B 6 07272B DCN6552 ...
Page 327: ...APPENDIX D Wire List and Electronic Schematics D 1 07272B DCN6552 ...
Page 328: ...This page intentionally left blank D 2 07272B DCN6552 ...
Page 332: ...This page intentionally left blank 07272B DCN6552 D 6 ...
Page 333: ...07272B DCN6552 D 7 ...
Page 338: ...07272B DCN6552 D 12 ...