2-18
Section 2 — Installation
3.
Line up the holes in the redundant supply case with the holes in the back of
the panel and install the supply with the screws provided.
4.
Attach the control cable from the redundant supply to the vacant connector
(J12) on the Distribution Board (068986) mounted to the right of the supply.
5.
Make sure the power switch on the front of the redundant supply is set to OFF.
Attach the ac line cord to the redundant connector on the back of the control
panel and connect it to an ac source.
6.
The Control Panel Power Supplies are auto-ranging; that is, they will
automatically adjust to operate on either 110 or 220 Vac nominal.
NOTE:
You may choose to install the redundant supply power into a different ac source
than the primary power supply; however, doing this is not required.
7.
Reinstall the ac power cord for the primary supply into its ac source.
8.
If you have installed this option into an existing system, turn on both power
supply switches for operation. No power supply adjustments are required at
this time.