7
Manual SD6
7.2.2.1
Line fuse
The mains fuse ensures line and power protection in the drive controller.
You can use the following protective devices:
•
Full range safety melt fuses for cable and circuit protection to IEC 60269-
2-1/DIN VDE 0636, part 201 NH fuses (operating class
gG
in accordance
with IEC operating class specification or
slow blow
in accordance with
VDE)
•
Circuit breaker with trigger characteristics C in accordance with EN 60898
•
Power circuit breaker
The following applies to size 3 (SD6A34, SD6A36, SD6A38):
Operation only with mains commutation reactors and mains fuse for operating
class gG (see section "Line fuses" > "Full range safety melt fuses").
UL-compliant line fuse
Use the following fuses for UL-compliant operation:
•
Fuses of class RK1, for example Bussmann KTS-R-xxA/600 V.
•
For drive controllers sizes and 1 you can also use fuses of class CC.
•
For drive controllers size 0 to 2 you can also use type E motor starters from
Eaton Industries, consisting of a motor protection switch and supply
terminal.
See the table below for suitable fuses:
Type
Input current
I
1N,PU
(8 kHz)
Input current
I
1N,PU
(4 kHz)
Recommended
mains fuse (max.)
SD6A02
5.9 A
8.3 A
10 A
SD6A04
2.2 A
2.8 A
10 A
SD6A06
4 A
5.4 A
10 A
SD6A14
9.3 A
12 A
16 A
SD6A16
15.8 A
19.2 A
20 A
SD6A24
24.5 A
26.4 A
35 A
SD6A26
32.6 A
38.4 A
50 A
SD6A34
37 A
45.3 A
50 A
SD6A36
62 A
76 A
80 A
SD6A38
76 A
76 A
80 A
Information
Note that these values apply only to the drive controllers that are
connected to the mains individually. Different parameters apply to
drive controllers in a Quick DC-Link system.
Type
Class CC
Class RK1
Type E motor starters
(Eaton Industries)
SD6A02
10 A
10 A
PKZM0-10/SP + BK25/3-PKZ0-E
SD6A04
10 A
10 A
PKZM0-10/SP + BK25/3-PKZ0-E
SD6A06
10 A
10 A
PKZM0-10/SP + BK25/3-PKZ0-E
SD6A14
15 A
15 A
PKZM0-16/SP + BK25/3-PKZ0-E
SD6A16
20 A
20 A
PKZM0-25/SP + BK25/3-PKZ0-E
SD6A24
–
35 A
PKZM0-32/SP + BK25/3-PKZ0-E
SD6A26
–
50 A
PKZM4-50 + BK50/3-PKZ4-E
SD6A34
–
50 A
–
SD6A36
–
80 A
–
SD6A38
–
80 A
–